Adding BACnet Parameters

A BACnet parameter maps one point (object) of a controller to a trackable data point in Enture. Once added, the platform reads the point continuously — and writes to it, if you set it up for that — and makes the value available for dashboards, reports, alerts, and real-time views.

Before you begin

  • The BACnet Device must already exist.
  • You need the object type and object number (instance) of each point, as listed in the controller's point list or its BACnet documentation. For example, "Analog Input 3" is the object type Analog input with object number 3.
  • You need Engineer access to create parameters.

Steps

1. Open the BACnet Device

In the left sidebar, go to Digital Twin → Devices and open the device you want to add a parameter to.

2. Add a parameter

Click Create BACnet parameter.

3. Fill in the parameter details

Field Description
Name A descriptive name for this data point (e.g. Supply Air Temperature). Up to 40 characters.
Object type The kind of BACnet object: Analog, Binary or Multi-state, each as an Input, Output or Value
Object instance The object's number inside the controller, from 0 to 4194302
Access Read only, Write only, or Read and write. Input objects can only be read.
Write priority Only for points that can be written. See Write priority below.
Read every (seconds) How often the point is read. The default is 5 seconds.
Unit The engineering unit (e.g. °C, %, kW). Optional.
Data Processing Average, Difference (useful for counters), or Negative Difference
Description Notes about this parameter

The value type follows from the object type: analog points are numbers, binary points are on/off (1/0), and multi-state points are state numbers (1, 2, 3, …).

4. Common settings

Correction Factor, Idle Latency, Entropy, and the related checkboxes (Enable Entropy, Limit Entropy, Remove Negative Entropy, Remove Decimal, Restrict User Access, Calculate Consumption, Disabled) work the same way as on every other protocol — see Common Parameter Settings for details. For BACnet the Correction Factor can be any number except 0.

5. Save

Click Create. The parameter is added to the device.

Each point on a controller can be added to a device only once.

Write priority

BACnet controllers rank the commands they receive on a scale from 1 (strongest) to 16. When several commands are active on the same point, the controller follows the strongest one. This has two consequences for you:

  • A value you write is overridden by any stronger command — for example from the building management system. The point then keeps the stronger command's value, even though your command was accepted. Always check the live value to see what the controller is actually using.
  • A value you write stays in force until you release control (see below) or something stronger takes over.

Choose the level your commands should use when you set the point up:

  • 8 is the usual level for a person at a console, and is the default.
  • Levels 1, 2 and 6 are reserved — 1 and 2 for life-safety functions, and 6 for the controller's own minimum on/off timing — and cannot be selected.
  • Use a smaller number (3–5, 7) only if you want your command to win against more of the building system's own commands.

Writing a value or releasing control

A point shows a write area on its detail page when it is set to Write only or Read and write, writing is enabled for the parameter, and you have the Write permission.

Sending a value

  1. Open the parameter's detail page (click the parameter name on the device).
  2. In the Write area, enter the value:
    • Analog points — type a number.
    • Binary points — click On or Off.
    • Multi-state points — type the state number (1 or higher).
  3. Click Send.

Enture confirms that the command was sent. It does not wait for the controller to confirm it, so check the live value on the same page to see the result — especially if the point may also be commanded by the building management system.

Releasing control

Writing a value never gives control back by itself. To hand the point back to the building system, click Release control. Your command is removed, and the point returns to whatever the controller's own logic or a weaker command dictates.

Switching writing on or off

When you add a point as Write only or Read and write, writing is switched on. A user with engineer access can switch it off and on again with the Disable Write / Enable Write button on the parameter's detail page — useful as a quick safeguard while maintenance is in progress. Changing the point's other settings does not switch writing back on. A point set to Read only can never be written, and writing cannot be enabled for it.

What happens next

The edge device receives the updated parameter list within approximately 30 seconds and begins reading the point.

Viewing live data

  1. Navigate to Digital Twin → Devices → open the device.
  2. Click on the parameter name.
  3. The parameter detail page shows the current value and a real-time chart.

Tip

If you do not see data arriving after a few minutes, verify that:

  • The controller's IP address and port are correct and the controller is reachable from the edge device.
  • A firewall between them allows BACnet/IP traffic (UDP port 47808 by default).
  • The object type and object number match the controller's point list exactly.
  • The parameter is not set to Disabled.

Tip

If a value you write does not take effect, the point may be under a stronger command from the building management system, or the controller may have refused the value. Check the live value, and ask whoever manages the building system whether the point is being commanded elsewhere.

Updating or deleting a parameter

On the device, use the edit and delete actions on the parameter. An existing parameter's device cannot be changed.